TN DA103 Troubleshooting PLC Port Communication Errors in Wonderware DAServers

Last updated: March 3rd, 2025

Description

  • Author: Brian Schneider
  • Published: March 3rd, 2025

Details:

Description

This article may help when the DA Server fails to communicate with one or more PLC's and port related errors are found in the Log Viewer for the DA Server.

Detailed Steps 

Each of the DA Servers utilizes a specific port when communicating with the PLC via TCP/IP. Below is a list of the ports used by the most common DA Servers.

DA Server Port Number
DASABCIP 44818
DASABTCP 2222
DASMBTCP 502
DASSIDIRECT 102

Sometimes the port is blocked by a firewall or the PLC is not listening on that port. You may encounter a port refused error in the Wonderware Log Viewer. Microsoft has a utility that may be used for checking the IP address and port number of the PLC. 

The download may be found at the following link:

http://www.microsoft.com/en-us/download/details.aspx?id=17148

Run the PortQryV2.exe installer on the DA Server machine. 

Click the Yes button to accept the license agreement.

Extract the required files by clicking the Unzip button and then click the close button.

The application is installed to the PortQryV2 folder on the C drive.

Open the command prompt by typing in CMD from the start button search and press enter.

Type in portqry –n <PLC IP address> -e <port number> and the enter key.

The PortQryV2 application will return one of the following responses:

LISTENING – everything appears to be good for PLC communication.

NOT LISTENING – check to be sure you have the correct port number. A PLC configuration change may be required. This may involve a firmware update.

FILTERED – Check the network firewall to be sure the port is not blocked.

plc daservers
Give feedback about this article

Recommended articles

Connecting to RSLinx with FSGateway

Read More

DAServer is missing in the DAServer Manager after installation or changing account password.

Read More

How to monitor a PLC Connection from Kepserver using Wonderware Intouch

Read More

TN DA101 FSGateway: Failed to create OPCEnum error

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Logo

© 2025 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand