TN AppSvr325 Check-list For Troubleshooting Failed Deployment Attempts on Industrial Application Server version 2017 Update 3

Last updated: March 17th, 2026

Description

  • Author: Brian Schneider
  • Published: March 17th, 2026

Details:

Description

This article from InSource shows a Checklist for troubleshooting failed deployment attempts on Industrial Application Server version 2017 Update 3

  • Author: Peter Farrell
  • Published: 6/17/2019
  • Applies to: Industrial Application Server 2017 Update 3

Details

Checklist for troubleshooting failed deployment attempts on Industrial Application Server version 2017 Update 3. This is not a complete list of possible causes for a failed deployment, but it should resolve most issues that are causing problems. 

To resolve failed to deploy on each of the target platforms

  1. Run the OS Configuration Utility
    From Search look for OSConfiguration
    Reboot
  2. Run the Change Network Account UtilityReboot
  3. Disable User Access Control (UAC) by pulling the slider to the bottom – never notify
  4. Confirm that DCOM is enabled from within DCOMcnfg navigate to Component Services > Computers > My Computer
    Right-click on My Computer and click Properties.
    On the Default Properties tab click the option for “Enable Distributed COM on this computer”
  5. Check to ensure that each of the following services are running and set to automatic
    A Bootstrap
    ArchestrA Watchdog Service
  6. Check the network adapter priority settings (formally network binding order). The Interface Metric from within IPv4 Properties > Advanced settings should be the lowest of all interfaces on the machine.
  7. Disable IPv6
  8. Flush DNS – Start a command prompt and enter the following

    ipconfig /flushdns
     
  9. Use Wonderware Tech Alert number TA385 available on the Aveva Technical Support site at the URL shown below to add the following folders if missing:

https://sw.aveva.com/support/wonderware

Login as a user with administrative rights.
Check to see if the following directory exists: C:\Windows\Serviceprofiles\aaPIM. If it does, check to see if it has the following sub-directory: \AppData\Local\Temp. It will appear as shown here:

C:\Windows\Serviceprofiles\aaPIM\AppData\Local\Temp.

If the sub-directories do not exist, create them.

Repeat the above steps for the following directories.
C:\windows\Serviceprofiles\AIMToken
C:\windows\Serviceprofiles\ArchestrADataStore
C:\windows\Serviceprofiles\AsbServiceManager
C:\windows\Serviceprofiles\InTouchDataService
C:\windows\Serviceprofiles\InTouchWeb
C:\windows\Serviceprofiles\Watchdog_Service
C:\windows\Serviceprofiles\aahClientAccessPoint
C:\windows\Serviceprofiles\aahSupervisor

Reboot the machine
 

  1. Enabling "everyone permissions" for anonymous users. To enable these permissions, go to: Local Security Policy > Local Policies > Security Options > Network Access: Let everyone permissions apply to anonymous

Right-click and enable “Network Access: Let everyone permissions apply to anonymous”

  1. If running Windows 10 or Windows Server 2016, from within the IDE > Platform configuration > General tab ensure that the platform network address does NOT include an underscore in the server name.

Note that naming conventions for server name is more rigid that it once was. See the following article for more information:

https://en.m.wikipedia.org/wiki/Hostname

“While a hostname may not contain other characters, such as the underscore character (_), other DNS names may contain the underscore.”

troubleshooting deployment
Give feedback about this article

Recommended articles

TN 1394 Error when Deploying: Remote Node's UserID/Password don't match GR Node's

Read More

TN 1366 Managing your Standalone InTouch Application in the Galaxy

Read More

TN - AppSrv - 16040702 Resolving "Open: Memory on the computer is low. New editor can't be launched."

Read More

TN 1040 No Alarms in Window Viewer

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand