Some content on this site is available only to logged-in subscribers. Contact Us for information on becoming a subscriber.

InSource.Solutions | InSource Training | InSource Client Portal
InSource Solutions Logo
Log In Sign Up
InSource.Solutions InSource Training InSource Client Portal Log In Sign Up
  • Home
  • AVEVA Application Server
  • AVEVA Application Server Tech Notes

TN AppSvr242 How to Manually Remove a Platform

Last updated: February 26th, 2025

Description

  • Author: Brian Schneider
  • Published: February 26th, 2025

Details:

Description

This article from InSource shows How to Manually Remove a Platform

  • Author: Benjamin Davis
  • Published: 06/28/2017
  • Applies to: Application Server

Details

You should first try to run Platform Killer to remove the platform. However, sometimes even after running Platform Killer, you are still unable to deploy a platform to the target computer.

You can then manually remove the platform by deleting its folder from the registry.

The path is HKLM\Software\Wow6432Node\ArchestrA\Framework\Platform\PlatformNodes

 

platform removal manual process
Give feedback about this article

Recommended articles

TN 1394 Error when Deploying: Remote Node's UserID/Password don't match GR Node's

Read More

TN 1366 Managing your Standalone InTouch Application in the Galaxy

Read More

TN - AppSrv - 16040702 Resolving "Open: Memory on the computer is low. New editor can't be launched."

Read More

TN 1040 No Alarms in Window Viewer

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand