TN 1199 General Deployment Failure with Keberos Enabled

Last updated: February 20th, 2025

Description

  • Author: Rich Brooks
  • Published: February 20th, 2025

Details:

Description

This article from InSource shows to resolve a general deployment failure for AVEVA Application Server when Kerberos authentication is enabled. 

  • Author: Rich Brooks
  • Published: 12/1/2021
  • Applies to: AVEVA Application Server 2020 R2 SP1

Details

The galaxy repository node deploys successfully. All other platforms fail to deploy with a "General Deployment Failure". The following error messages are found in the Log Viewer as a result of the failed deployment.

These error messages indicate there is a problem in copying the files required for deployment from the IDE. The registry edits do complete successfully during deployment to the remote nodes. A Wireshark trace on the network traffic identifies a Keberos authentication problem.

Kerberos Authentication was found to be enabled in the Local Security Policy Security Options. It was set as a default domain policy GPO.

The network service account used for deployment was not set up to support Kerberos. It is critical that the following two check boxes are checked to allow the user to authenticate with the remote nodes.

Allowing the network account to support Kerberos resolved the deployment issue.

deployment issue kerberos error
Give feedback about this article

Recommended articles

TN 1394 Error when Deploying: Remote Node's UserID/Password don't match GR Node's

Read More

TN 1366 Managing your Standalone InTouch Application in the Galaxy

Read More

TN - AppSrv - 16040702 Resolving "Open: Memory on the computer is low. New editor can't be launched."

Read More

TN 1040 No Alarms in Window Viewer

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand