Platform_X_exceed_maximum_heartbeats

Last updated: March 19th, 2025

Description

  • Author: Frank Ross
  • Published: March 19th, 2025

Details:

Description

The Aveva (Wonderware) System Platform (App Server) environment is sustaining periodic lockups or freezes. The result of which is potentially the HMIs are not responsive and data is not historizing. Additional analysis into the Systems Management Console (SMC) shows repeated warnings of "Platform x exceed maximum heartbeats timeout". 

The communication error message Platform X exceed maximum heartbeats timeout of Y ms occurs when the response time between platforms is greater than the Message Exchange time set in the IDE's Platform configuration.

  • Author: Frank Ross
  • Published: 09/21/2022
  • Applies to: Wonderware (Aveva) Application Server (all versions)

Details

This issue is occurring most likely to a disruption in the network external to the System Platform environment. The recommendation is to have the customer’s network and IT support team identify the device(s) that is causing the issue. A log of each event should be documented which tracks the date, time, and duration of outage. Windows logs should also be captured as additional supporting evidence. Capturing this log information hopefully will help trace the root cause of the offending network appliance(s).

The other potential reason which could cause this issue is with the configuration of the platform heartbeat period frequency and consecutive missed heartbeats. Details on how to reconfigure the heartbeat period and missed heartbeats can be found in Aveva article: https://softwaresupportsp.aveva.com/#/okmimarticle/docid/tn000022856

Note: If the "Platform x exceed maximum heartbeats timeout" only occurs sporadically, and does not appear to be causing any service disruptions, take no action to remediate. It is when when the SMC is repeating this warning log continuously over short periods (measured in minutes), that remediation action should be taken.

Give feedback about this article

Recommended articles

TN 1394 Error when Deploying: Remote Node's UserID/Password don't match GR Node's

Read More

TN 1366 Managing your Standalone InTouch Application in the Galaxy

Read More

TN - AppSrv - 16040702 Resolving "Open: Memory on the computer is low. New editor can't be launched."

Read More

TN 1040 No Alarms in Window Viewer

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand