This article from InSource shows how licensing DA and OI servers works with Wonderware 2017. 

  • Author: Ernest Lee
  • Published: 12/19/2017
  • Applies to: Wonderware System Platform 2017

Details

With Wonderware 2017 comes a new licensing procedure which involves using a .xml file instead of the .lic file normally used to license the product. See link for a video on how this new licensing process works. 

Take note that the .xml file does not license OI and DA servers.

There is a ArchestrA.lic file that has feature lines for OI and DA Servers. 

FEATURE DAServer Wonderware 11.1 1-jan-00 uncounted \
    VENDOR_STRING=count:1 HOSTID=ANY ISSUER="Invensys Systems, \
    Inc." NOTICE=

FEATURE OI_Server Wonderware 11.1 1-jan-00 uncounted \
    VENDOR_STRING=count:1 HOSTID=ANY ISSUER="Invensys Systems, \
    Inc." NOTICE=

Install this license using the ArchestrA License Manager as done in previous versions to enable full functionality of  OI and DA servers.