Skip to main content
InSource Solutions

TN IT299 How to have different applications selectable for different users in Intouch Access Anywhere

InSource_Logo_Transparent (1).png

 

Description

 

This article from InSource walks through a process for displaying different selectable applications for different users in Intouch Access Anywhere.

  • Author: Joseph Hefner
  • Published: 11/15/2017
  • Applies to: InTouch Access Anywhere 2014 R2

Details

This article walks through a process for displaying different selectable applications for different users in Intouch Access Anywhere.

 

  1. Navigate to C:\Program Files (x86)\Wonderware\InTouch Access Anywhere Server\WebServer\AccessAnywhere 
  2. Create 2 copies of the Start.html file and name them startA.html and startB.html
  3. Open startA.html in notepad and delete the entries that you do not wish to be selectable for User A. In the example below only the demo1.aareactordemo application will remain selectable.

Capture1.jpg

4. Open startB.html in notepad and delete the entries that you do not wish to be selectable for User B. 

5. Provide startA.html url \\Serververname:8080\StartA.html to UserA and startB.html url \\Serververname:8080\StartB.html to UserB.