TN IT253 Setting Up A Local I/O Tag To A Remote Application

InSource_Logo_Transparent.png

Description

This article from InSource Solutions shows you how to set up a local InTouch I/O tag to read a tag in a remote InTouch application.

  • Author: Daniel London
  • Published: 03/02/2017
  • Applies to: InTouch

Details

It is possible to reference a tag in a remote application (one running on another computer) inside of a local InTouch application on a different machine. To do so, you will first have to set up an access name to the WindowViewer session on the remote machine. The second part involves creating an I/O tag in the local application that references the tag you are trying to read in the remote application.

NOTE: WindowViewer must be running the application on the remote machine for the live value to update.

  1. In the local application set up a new access name following the example below.

Node Name: <Host Name / IP of remote machine>

Application Name: VIEW

Topic Name: tagname

Capture1.jpeg

  1. In the local application create a new I/O tag in the Tagname Dictionary that references the InTouch tag on the remote system/application.

Access Name: Access name you mapped to the remote InTouch application.

Item: Tag name of the tag in the remote InTouch application.

Capture2.jpeg