TN IT172 How to change port number in Intouch Access Anywhere
Description
Changing the port number for Intouch Access Anywhere
- Author: Ernest Lee
- Published: 11/25/2015
- Applies to: Intouch 10.6 and later
Details
To change the Port on the Configuration Dialog
- Open the configuration dialog and click the Communication tab.
- Change the port number from 8080 (default) to 9090.
Figure 1 (below) shows the change from the default port to Port 9090.
- Figure 1: Change Port Number in Configuration Dialog
- Click OK.
- The InTouch Access Anywhere services will be restarted.
- Go to the file config.js which is located under:
• 32-bit machine: C:\Program Files\Wonderware\InTouch Access Anywhere Server\WebServer\AccessAnywhere\
• 64-bit machine: C:\Program Files (x86)\Wonderware\InTouch Access Anywhere Server\WebServer\AccessAnywhere\ - Change the setting of the wsport item from 8080 to 9090 in the config.js file under C:\Program Files (x86)\Wonderware\InTouch Access Anywhere Server\WebServer\AccessAnywhere\ (Figure 2 below).