TN IT123 Tagname Dictionary - alarm option unavailable
Description
In the Wonderware InTouch Tagname Dictionary, the option to enable Alarms is grayed out.
- Author: Ernest Lee
- Published: 04/10/2015
- Applies to: Intouch 2012 - 2014R2
Details
In the Wonderware InTouch Tagname Dictionary, if the option to enable alarming at the top is unavailable this means that Intouch is being used as a view application.
You can check this by launching InTouch WindowMaker and at the top go to Special -> Application Type. There you will see a check in the InTouchView Application box.
When the View Application is enabled you would need to use object based alarms in the IDE running on another node in your Galaxy.