TN - 1364 Enabling Mixed Mode Within the System Management Server

Description

 

This article from InSource shows how to enable mixed mode authentication within the System Management Server and how it changes your System Platform installation

  • Author: Justin Benton
  • Published: 5/17/2023
  • Applies to: System Platform 2023 

Details

The System Management Server is an encryption service that was introduced in System Platform in order to encrypt intranet Suitelink communications. Doing so makes your environment more secure when it comes to System Platform software communicating from node to node. However, in System Platform 2023, you now have the option to encrypt communications while accepting unencrypted communications from third party software. For example, Win 911 uses a Suitelink connection in order to capture alarm data and provide its functionality to customer. In order for certain programs to use Suitelink while the SMS is active, you may need to enable mixed mode, here's how:

 

1. Open the Configurator and navigate to the Common Platform>System Management Server section

clipboard_e9fa8ff153adaeb6a94d4538395e25b4c.png

 

2. Click "Advanced" and then the "Communications" tab

clipboard_ecc547df68fec1190338e22a2b99e70c7.png

 

3. Check "Accept non-encrypted Suitelink connections. This will enabled mixed mode after a reboot