Client Pen Trend or Tagname Dictionary Appears on a Secondary Screen to WindowMaker

HOWTOSMALL.jpg
HOW TO

 

 

When developing in Window Maker sometimes when you open the tagname dictionary or double click on an Active X and the configuration window appears on a secondary monitor. This   causes problems when you place an Application on a single monitor screen as you are unable to see this. Below are the steps to resolve this.

 

1 Close down WindowMaker and WindowViewer.

 

2 Open InTouch Application Manager to see where you application is residing.

 

1.png

3 Browse to the application directory and in the folder there will be a file called tagbrw.dat

 

2.JPG

 

 

4 Rename this file to .old and then launch your WindowMaker.  