TN DA110 DASMBTCP Zero Based Addressing Errors not defined option is grayed out

insource logo large.jpg

 

When trying to configure the DA Server DASMBTCP version 3.0 and above in the SMC you get Zero Based Addressing Errors stating not defined with handle 0 or the option is grayed out.

 

  • Author: Alex Davenport
  • Published: 04/17/2015
  • Applies to: DASMBTCP 3.0 and above

 

 

When you try to configure the DASMBTCP 3.0 DA Server in the SMC you get the below errors.

 

Zero1.JPG

Zero2.JPG

 

Or you see the following option is greyed out.

 

Zero3.JPG

 

The cause of this is that you’ve copied in the configuration files from an older version of the DA Server in the below location and have the incorrect DASMBTCP.AArul file.

 

Browse to the C:\ProgramData\Wonderware\DAServer\DASMBTCP directory and remove the old DASMBTCP.AArul file then copy in from the installation files the later version.

 

Zero4.JPG

 

As you see below the option isn’t greyed out and you won’t get the error messages previously seen.

 

Zero5.JPG