Skip to main content
InSource Solutions

TN DA104 IO Server cannot be configured after being set to run as Service

insource logo large.jpg

 

Description

After Setting a Wonderware IO Server as a service it cannot be configured. 

 

  • Author: Mike Viteri
  • Published: 03/11/2015
  • Applies to: Wonderware IO Servers (Not DA/Data Access Servers)

 

 

Details

After Setting an IO Server as a service it cannot be configured

 

Resolution

 Go into REGEDIT \HKEY_Local_Machine\Software\Wonderware\YourIODriver\ delete the NTService Key. Then Reboot