TN DA114 Correct TSAP Settings for Siemens S7-1200 PLC

insource logo large.jpg

 

Description

  • Author: Daniel London
  • Published: 05/21/2015
  • Applies to: DASSIDirect (All Versions)

 

Details

When configuring a DASSIDirect PLC driver for the DA Server, it is imperative to have the correct Transport Service Access Point (TSAP) settings for the driver.

The correct TSAP settings for the Siemens S7-1200 PLC are shown below....

Local TSAP: 1, 0

Remote TSAP: 0, 1

Connection Resource: 3