TN Appsvr114 Failed to Connect to AppServer GR Node
Tech Note
Description
The following issue is sometimes seen as a result of using the Platform Remover with Wonderware System Platform - Application Server. This is caused by registry keys not being deleted properly. It is necessary to delete the remaining registry keys in order to create a new galaxy.
- Author: Rich Brooks
- Published: 11/12/2014
- Applies to: Application Server v4.0 and higher
How and When to Use this Guide
This tech note should only be used when a popup error message similar to the one shown below is seen during new galaxy creation.
Instructions
Open the registry editor by typing REGEDIT from a command prompt and then press Enter.
The registry editor opens. Browse to the first key.
HKEY_LOCAL_MACHINE\SOFTWARE\Wow6432Node\ArchestrA\ArchestrAServices\Archestra_xxx
Highlight and delete the registry key as shown above.
Browse to the second key.
HKEY_LOCAL_MACHINE\SOFTWARE\Wow6432Node\ArchestrA\ArchestrAServices\Node_Registration
Highlight and delete the registry key as shown above.
Confirmation of Success
The New Galaxy button should now operate as expected.