Backing up an InTouch application
Overview
Have developed an InTouch application and want to create a backup for recovery purposes, or for moving the application to a different system.
Resolution
There are a few ways to backup InTouch applications, depending on what type of application is used and how the backup is intended to be used in future.
Backing up the Tagname Dictionary:
Stand-Alone and Published InTouch applications:
- Shutdown WindowMaker or WindowViewer if either is currently running.
- Open InTouch Application Manager by going to Start > Programs > Wonderware > InTouch.
- A list of applications will be displayed. Right click on the application you are concerned with and select DB Dump.
- Select where the file should be saved, and the name it should have, and then press the OK button.
Managed InTouch applications:
- Shutdown WindowMaker or WindowViewer if either is currently running.
- Open the ArchestrA IDE if it is not already running, but going to Start > Programs > Wonderware > ArchestrA IDE.
- Select the appropriate Galaxy and press the Connect button.
- In the Template Toolbox find your InTouchViewApp template object.
- Ensure the object is currently Checked In.
- Right click on the object and go to Export > DB Dump.
- Select where the file should be save, and the name it should have, then press the OK button.
Backing up the entire InTouch application:
Stand-Alone and Published InTouch applications:
- Shutdown WindowMaker or WindowViewer if either is currently running.
- Open InTouch Application Manager by going to Start > Programs > Wonderware > InTouch.
- A list of applications will be displayed. Find the column labeled Path, and note the location.
- Open Windows Explorer and browse to this folder on the hard drive.
- Right click this folder and either copy and paste it to a new location, or right click and select Send To > Compressed (zipped) Folder. This will create a compressed copy of your application.
Managed InTouch applications:
- Shutdown WindowMaker or WindowViewer if either is currently running.
- Open the ArchestrA IDE if it is not already running, by going to Start > Programs > Wonderware > ArchestrA IDE.
- Select the appropriate Galaxy and press the Connect button.
- In the Template Toolbox find your InTouchViewApp template object.
- Ensure the object is currently Checked In.
- Right click on the object and go to Export > Object.
- Select where the file should be saved, and the name it should have, and then click the Save button.