TN AppSvr245 How to make sure an individual item within an OPC Client object will always be active

InSource_Logo_Transparent.png

Description

 

This article from InSource shows how to make sure an individual item within an OPC Client object will always be active.

  • Author: Joseph Hefner
  • Published: 5/18/2017
  • Applies to: Application Server 2014 R2 and later

Details

Step 1)

Within the OPC Client object click the Scan Group tab and click the "+" button if a scan group does not currently exist:

Capture1.jpeg

 

Step 2)

Type the name of the OPC Device group and select an update interval. After that click the Scan Mode and choose "ActiveAll":

Capture2.jpeg

 

Capture3.jpeg

Step 3)

Click the "+" button in the associated attributes section to add a new attribute and give the associated attribute a name. In this example it is called "A1":

Capture4a.jpeg

 

Capture5.jpeg

 

Step 4)

Click the Attributes tab and create a new attribute to link to the associated attribute from the OPC device group:


Capture6.jpeg

Step 5)

Give the attribute a name and select the I/O button:

Capture7.jpeg

Step 6)

Click the Save button and then click the browse button in the I/O section:

Capture8a.jpeg

 

Step 7)

Select the relative reference icon on the top and then select the newly added associated attribute and click the "OK" button:

Capture9.jpeg

Step 8)

Click the "Save and Close" icon and then check the object in and deploy:

Capture10.jpeg

 

Capture11.jpeg