TN - 1349 When configuring MES BI Gateway Reports you get an message "error occurred while executing the script"
Description
- Author: Mike Viteri
- Published: 3/28/2023
- Applies to: MES 2023
Details
When configuring MES BI Gateway Reports you get an message "error occurred while executing the script"
When trying to configure BI Gateway Reports in configurator you the "error occurred while executing the script"
This message happens because the BI Model has not been imported.
go to the website https://yourservername:61075
Click on Import Model
You will now Import the Model
Import MESIntelligenceModel.json from C:\Program Files (x86)\Wonderware\MES\BI Gateway Reports
Click Import(if the reboot does not work. You might have to reboot.)
You should see Import Successfully and see Measures Dimensions and Data Sources.
Deploy your Model.
Now you can configure the BI Gateway Reports
BI Gateway Reports are configured.