TN HistClient141 Historian Client Silent Install

InSource_Logo_Transparent.png

Description

 

This article from InSource shows how to silently install the Wonderware Historian Client.  The Historian Client is often installed for a large number of users.  This provides command line options for installation that may be used by IT to push out the application to each machine.

  • Author:  Rich Brooks
  • Published:  9/24/2018
  • Applies to:  Wonderware Historian Client 2014R2 SP1 and higher

Details

The Historian Client is installed using the Wonderware System Platform DVD or ISO file.  Type Setup /? from a command prompt to see the installation switches.

A response file is used to select the options for the installation.  Browse to the \InstallFiles\ResponseFiles\Samples folder for example response files.

Capture2.JPG

We will use the Historian Client.txt file as a bootstrap is not required.  Open the text file in Notepad to edit the XML format text file.

Capture3.JPG

Edit the UserName and Password to enter the ArchestrA user credentials.

<responsefile>
<install>
AdminUserForm.SUserName=ArchestrAUser
AdminUserForm.SPassword=Password123
AdminUserForm.SCreateLocal=true
FeatureForm.SFeatureList=Historian Client.Medusa,Licensing.LicenseManager
FeatureForm.SInstallDir=C:\Program Files (x86)
</install>
</responsefile>

Use the silent installation syntax to install the Historian Client from a command line or batch file.

<DVD>:\setup.exe /silent “<path\Historian Client.text>”

 

The installation will run without any responses required from the user.