Skip to main content
InSource Solutions

TN Hist283 How to change the Interpolation type for all Integer tags in the Wonderware Historian.

Description

 

This article from InSource walks through a process for changing the Interpolation Type for all integer tags in the Wonderware Historian.

  • Author: Joseph Hefner
  • Published: 11/21/2017
  • Applies to: Historian 10 and above.

Details

By default, the Wonderware Historian returns all Integer values with the "Stairstep" Interpolation type. This tech note walks through the process for switching to "Linear".


Step 1)  Launch the System Management Console and navigate to the Configuration Editor \ System Configuration \ Parameters:

Capture1.JPG

 

 

 

Step 2) Find the parameter InterpolationTypeInteger and double click on it:

 

Capture2b.JPG

 

Step 3)  Type in a value of 1 for Linear Interpolation and click "Apply" and then "OK".   If you wish to switch to stairstep Interpolation you would enter a value of 0 here.

 

Capture3b.JPG

 

Step 4) Right click on the Configuration Editor in the tree and choose "Commit Pending Changes":

Capture4.JPG

 

Step 5) Click the Commit button:

 

Capture5.JPG