TN Hist238 Historian Quality Detail Value and Description list
Description
The list below shows each quality detail value available in the Historian. It will also show what the description of the quality value.
- Author: Mike Viteri
- Published: 11/12/2015
- Applies to: Historian
Details
0 | Bad Quality of undetermined state |
1 | No data available, tag did not exist at the time |
2 | Running insert |
10 | Communication loss |
16 | Good value, received out of time sync (cyclic tag) |
17 | Duplicate time stamp; infinite slope |
20 | IDAS overflow recovery |
24 | IOServer communication failed |
33 | Violation of History Duration license feature |
44 | Pipe reconnect |
64 | Cannot convert |
150 | Storage startup |
151 | Store forward storage startup |
192 | Good |
202 | Good point of version Latest |
212 | Counter rollover has occurred |
248 | First value received in store forward mode |
249 | Not a number |
252 | First value received from IOServer |
256 | Bad Quality of undetermined state, timestamp overwritten; values in future |
257 | No data available, tag did not exist at the time, timestamp overwritten; values in future |
258 | Running insert, timestamp overwritten; values in future |
266 | Communication loss, timestamp overwritten; values in future |
272 | Good value, received out of time sync (cyclic tag), timestamp overwritten; values in future |
273 | Duplicate time stamp; infinite slope, timestamp overwritten; values in future |
276 | IDAS overflow recovery, timestamp overwritten; values in future |
280 | IOServer communication failed, timestamp overwritten; values in future |
300 | Pipe reconnect, timestamp overwritten; values in future |
320 | Cannot convert, timestamp overwritten; values in future |
406 | Storage startup, timestamp overwritten; values in future |
407 | Store forward storage startup, timestamp overwritten; values in future |
448 | Good, timestamp overwritten; values in future |
458 | Good point of version Latest, timestamp overwritten; values in future |
468 | Counter rollover has occurred, timestamp overwritten; values in future |
504 | First value received in store forward mode, timestamp overwritten; values in future |
505 | Not a number, timestamp overwritten; values in future |
508 | First value received from IOServer, timestamp overwritten; values in future |
512 | Bad Quality of undetermined state, timestamp overwritten; values out of time sequence |
513 | No data available, tag did not exist at the time, timestamp overwritten; values out of time sequence |
514 | Running insert, timestamp overwritten; values out of time sequence |
522 | Communication loss, timestamp overwritten; values out of time sequence |
528 | Good value, received out of time sync (cyclic tag), timestamp overwritten; values out of time sequence |
529 | Duplicate time stamp; infinite slope, timestamp overwritten; values out of time sequence |
532 | IDAS overflow recovery, timestamp overwritten; values out of time sequence |
536 | IOServer communication failed, timestamp overwritten; values out of time sequence |
556 | Pipe reconnect, timestamp overwritten; values out of time sequence |
576 | Cannot convert, timestamp overwritten; values out of time sequence |
662 | Storage startup, timestamp overwritten; values out of time sequence |
663 | Store forward storage startup, timestamp overwritten; values out of time sequence |
704 | Good, timestamp overwritten; values out of time sequence |
714 | Good point of version Latest, timestamp overwritten; values out of time sequence |
724 | Counter rollover has occurred, timestamp overwritten; values out of time sequence |
760 | First value received in store forward mode, timestamp overwritten; values out of time sequence |
761 | Not a number, timestamp overwritten; values out of time sequence |
764 | First value received from IOServer, timestamp overwritten; values out of time sequence |
1024 | Bad Quality of undetermined state, timestamp overwritten; server timestamping selected |
1025 | No data available, tag did not exist at the time, timestamp overwritten; server timestamping selected |
1026 | Running insert, timestamp overwritten; server timestamping selected |
1034 | Communication loss, timestamp overwritten; server timestamping selected |
1040 | Good value, received out of time sync (cyclic tag), timestamp overwritten; server timestamping selected |
1041 | Duplicate time stamp; infinite slope, timestamp overwritten; server timestamping selected |
1044 | IDAS overflow recovery, timestamp overwritten; server timestamping selected |
1048 | IOServer communication failed, timestamp overwritten; server timestamping selected |
1068 | Pipe reconnect, timestamp overwritten; server timestamping selected |
1088 | Cannot convert, timestamp overwritten; server timestamping selected |
1174 | Storage startup, timestamp overwritten; server timestamping selected |
1175 | Store forward storage startup, timestamp overwritten; server timestamping selected |
1216 | Good, timestamp overwritten; server timestamping selected |
1226 | Good point of version Latest, timestamp overwritten; server timestamping selected |
1236 | Counter rollover has occurred, timestamp overwritten; server timestamping selected |
1272 | First value received in store forward mode, timestamp overwritten; server timestamping selected |
1273 | Not a number, timestamp overwritten; server timestamping selected |
1276 | First value received from IOServer, timestamp overwritten; server timestamping selected |
2048 | Bad Quality of undetermined state, intermediate point stored by deadband storage algorithm |
2049 | No data available, tag did not exist at the time, intermediate point stored by deadband storage algorithm |
2050 | Running insert, intermediate point stored by deadband storage algorithm |
2058 | Communication loss, intermediate point stored by deadband storage algorithm |
2064 | Good value, received out of time sync (cyclic tag), intermediate point stored by deadband storage algorithm |
2065 | Duplicate time stamp; infinite slope, intermediate point stored by deadband storage algorithm |
2068 | IDAS overflow recovery, intermediate point stored by deadband storage algorithm |
2072 | IOServer communication failed, intermediate point stored by deadband storage algorithm |
2092 | Pipe reconnect, intermediate point stored by deadband storage algorithm |
2112 | Cannot convert, intermediate point stored by deadband storage algorithm |
2198 | Storage startup, intermediate point stored by deadband storage algorithm |
2199 | Store forward storage startup, intermediate point stored by deadband storage algorithm |
2240 | Good, intermediate point stored by deadband storage algorithm |
2250 | Good point of version Latest, intermediate point stored by deadband storage algorithm |
2260 | Counter rollover has occurred, intermediate point stored by deadband storage algorithm |
2296 | First value received in store forward mode, intermediate point stored by deadband storage algorithm |
2297 | Not a number, intermediate point stored by deadband storage algorithm |
2300 | First value received from IOServer, intermediate point stored by deadband storage algorithm |
2304 | Bad Quality of undetermined state, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2305 | No data available, tag did not exist at the time, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2306 | Running insert, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2314 | Communication loss, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2320 | Good value, received out of time sync (cyclic tag), timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2321 | Duplicate time stamp; infinite slope, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2324 | IDAS overflow recovery, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2328 | IOServer communication failed, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2348 | Pipe reconnect, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2368 | Cannot convert, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2454 | Storage startup, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2455 | Store forward storage startup, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2496 | Good, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2506 | Good point of version Latest, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2516 | Counter rollover has occurred, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2552 | First value received in store forward mode, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2553 | Not a number, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2556 | First value received from IOServer, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm |
2560 | Bad Quality of undetermined state, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2561 | No data available, tag did not exist at the time, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2562 | Running insert, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2570 | Communication loss, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2576 | Good value, received out of time sync (cyclic tag), timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2577 | Duplicate time stamp; infinite slope, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2580 | IDAS overflow recovery, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2584 | IOServer communication failed, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2604 | Pipe reconnect, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2624 | Cannot convert, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2710 | Storage startup, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2711 | Store forward storage startup, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2752 | Good, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2762 | Good point of version Latest, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2772 | Counter rollover has occurred, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2808 | First value received in store forward mode, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2809 | Not a number, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
2812 | First value received from IOServer, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm |
3072 | Bad Quality of undetermined state, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3073 | No data available, tag did not exist at the time, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3074 | Running insert, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3082 | Communication loss, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3088 | Good value, received out of time sync (cyclic tag), timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3089 | Duplicate time stamp; infinite slope, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3092 | IDAS overflow recovery, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3096 | IOServer communication failed, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3116 | Pipe reconnect, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3136 | Cannot convert, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3222 | Storage startup, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3223 | Store forward storage startup, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3264 | Good, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3274 | Good point of version Latest, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3284 | Counter rollover has occurred, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3320 | First value received in store forward mode, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3321 | Not a number, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
3324 | First value received from IOServer, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm |
4096 | Bad Quality of undetermined state, partial cycle |
4097 | No data available, tag did not exist at the time, partial cycle |
4098 | Running insert, partial cycle |
4106 | Communication loss, partial cycle |
4112 | Good value, received out of time sync (cyclic tag), partial cycle |
4113 | Duplicate time stamp; infinite slope, partial cycle |
4116 | IDAS overflow recovery, partial cycle |
4120 | IOServer communication failed, partial cycle |
4140 | Pipe reconnect, partial cycle |
4160 | Cannot convert, partial cycle |
4246 | Storage startup, partial cycle |
4247 | Store forward storage startup, partial cycle |
4288 | Good, partial cycle |
4298 | Good point of version Latest, partial cycle |
4308 | Counter rollover has occurred, partial cycle |
4344 | First value received in store forward mode, partial cycle |
4345 | Not a number, partial cycle |
4348 | First value received from IOServer, partial cycle |
4352 | Bad Quality of undetermined state, timestamp overwritten; values in future, partial cycle |
4353 | No data available, tag did not exist at the time, timestamp overwritten; values in future, partial cycle |
4354 | Running insert, timestamp overwritten; values in future, partial cycle |
4362 | Communication loss, timestamp overwritten; values in future, partial cycle |
4368 | Good value, received out of time sync (cyclic tag), timestamp overwritten; values in future, partial cycle |
4369 | Duplicate time stamp; infinite slope, timestamp overwritten; values in future, partial cycle |
4372 | IDAS overflow recovery, timestamp overwritten; values in future, partial cycle |
4376 | IOServer communication failed, timestamp overwritten; values in future, partial cycle |
4396 | Pipe reconnect, timestamp overwritten; values in future, partial cycle |
4416 | Cannot convert, timestamp overwritten; values in future, partial cycle |
4502 | Storage startup, timestamp overwritten; values in future, partial cycle |
4503 | Store forward storage startup, timestamp overwritten; values in future, partial cycle |
4544 | Good, timestamp overwritten; values in future, partial cycle |
4554 | Good point of version Latest, timestamp overwritten; values in future, partial cycle |
4564 | Counter rollover has occurred, timestamp overwritten; values in future, partial cycle |
4600 | First value received in store forward mode, timestamp overwritten; values in future, partial cycle |
4601 | Not a number, timestamp overwritten; values in future, partial cycle |
4604 | First value received from IOServer, timestamp overwritten; values in future, partial cycle |
4608 | Bad Quality of undetermined state, timestamp overwritten; values out of time sequence, partial cycle |
4609 | No data available, tag did not exist at the time, timestamp overwritten; values out of time sequence, partial cycle |
4610 | Running insert, timestamp overwritten; values out of time sequence, partial cycle |
4618 | Communication loss, timestamp overwritten; values out of time sequence, partial cycle |
4624 | Good value, received out of time sync (cyclic tag), timestamp overwritten; values out of time sequence, partial cycle |
4625 | Duplicate time stamp; infinite slope, timestamp overwritten; values out of time sequence, partial cycle |
4628 | IDAS overflow recovery, timestamp overwritten; values out of time sequence, partial cycle |
4632 | IOServer communication failed, timestamp overwritten; values out of time sequence, partial cycle |
4652 | Pipe reconnect, timestamp overwritten; values out of time sequence, partial cycle |
4672 | Cannot convert, timestamp overwritten; values out of time sequence, partial cycle |
4758 | Storage startup, timestamp overwritten; values out of time sequence, partial cycle |
4759 | Store forward storage startup, timestamp overwritten; values out of time sequence, partial cycle |
4800 | Good, timestamp overwritten; values out of time sequence, partial cycle |
4810 | Good point of version Latest, timestamp overwritten; values out of time sequence, partial cycle |
4820 | Counter rollover has occurred, timestamp overwritten; values out of time sequence, partial cycle |
4856 | First value received in store forward mode, timestamp overwritten; values out of time sequence, partial cycle |
4857 | Not a number, timestamp overwritten; values out of time sequence, partial cycle |
4860 | First value received from IOServer, timestamp overwritten; values out of time sequence, partial cycle |
5120 | Bad Quality of undetermined state, timestamp overwritten; server timestamping selected, partial cycle |
5121 | No data available, tag did not exist at the time, timestamp overwritten; server timestamping selected, partial cycle |
5122 | Running insert, timestamp overwritten; server timestamping selected, partial cycle |
5130 | Communication loss, timestamp overwritten; server timestamping selected, partial cycle |
5136 | Good value, received out of time sync (cyclic tag), timestamp overwritten; server timestamping selected, partial cycle |
5137 | Duplicate time stamp; infinite slope, timestamp overwritten; server timestamping selected, partial cycle |
5140 | IDAS overflow recovery, timestamp overwritten; server timestamping selected, partial cycle |
5144 | IOServer communication failed, timestamp overwritten; server timestamping selected, partial cycle |
5164 | Pipe reconnect, timestamp overwritten; server timestamping selected, partial cycle |
5184 | Cannot convert, timestamp overwritten; server timestamping selected, partial cycle |
5270 | Storage startup, timestamp overwritten; server timestamping selected, partial cycle |
5271 | Store forward storage startup, timestamp overwritten; server timestamping selected, partial cycle |
5312 | Good, timestamp overwritten; server timestamping selected, partial cycle |
5322 | Good point of version Latest, timestamp overwritten; server timestamping selected, partial cycle |
5332 | Counter rollover has occurred, timestamp overwritten; server timestamping selected, partial cycle |
5368 | First value received in store forward mode, timestamp overwritten; server timestamping selected, partial cycle |
5369 | Not a number, timestamp overwritten; server timestamping selected, partial cycle |
5372 | First value received from IOServer, timestamp overwritten; server timestamping selected, partial cycle |
6144 | Bad Quality of undetermined state, intermediate point stored by deadband storage algorithm, partial cycle |
6145 | No data available, tag did not exist at the time, intermediate point stored by deadband storage algorithm, partial cycle |
6146 | Running insert, intermediate point stored by deadband storage algorithm, partial cycle |
6154 | Communication loss, intermediate point stored by deadband storage algorithm, partial cycle |
6160 | Good value, received out of time sync (cyclic tag), intermediate point stored by deadband storage algorithm, partial cycle |
6161 | Duplicate time stamp; infinite slope, intermediate point stored by deadband storage algorithm, partial cycle |
6164 | IDAS overflow recovery, intermediate point stored by deadband storage algorithm, partial cycle |
6168 | IOServer communication failed, intermediate point stored by deadband storage algorithm, partial cycle |
6188 | Pipe reconnect, intermediate point stored by deadband storage algorithm, partial cycle |
6208 | Cannot convert, intermediate point stored by deadband storage algorithm, partial cycle |
6294 | Storage startup, intermediate point stored by deadband storage algorithm, partial cycle |
6295 | Store forward storage startup, intermediate point stored by deadband storage algorithm, partial cycle |
6336 | Good, intermediate point stored by deadband storage algorithm, partial cycle |
6346 | Good point of version Latest, intermediate point stored by deadband storage algorithm, partial cycle |
6356 | Counter rollover has occurred, intermediate point stored by deadband storage algorithm, partial cycle |
6392 | First value received in store forward mode, intermediate point stored by deadband storage algorithm, partial cycle |
6393 | Not a number, intermediate point stored by deadband storage algorithm, partial cycle |
6396 | First value received from IOServer, intermediate point stored by deadband storage algorithm, partial cycle |
6400 | Bad Quality of undetermined state, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6401 | No data available, tag did not exist at the time, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6402 | Running insert, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6410 | Communication loss, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6416 | Good value, received out of time sync (cyclic tag), timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6417 | Duplicate time stamp; infinite slope, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6420 | IDAS overflow recovery, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6424 | IOServer communication failed, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6444 | Pipe reconnect, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6464 | Cannot convert, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6550 | Storage startup, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6551 | Store forward storage startup, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6592 | Good, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6602 | Good point of version Latest, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6612 | Counter rollover has occurred, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6648 | First value received in store forward mode, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6649 | Not a number, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6652 | First value received from IOServer, timestamp overwritten; values in future, intermediate point stored by deadband storage algorithm, partial cycle |
6656 | Bad Quality of undetermined state, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6657 | No data available, tag did not exist at the time, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6658 | Running insert, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6666 | Communication loss, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6672 | Good value, received out of time sync (cyclic tag), timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6673 | Duplicate time stamp; infinite slope, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6676 | IDAS overflow recovery, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6680 | IOServer communication failed, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6700 | Pipe reconnect, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6720 | Cannot convert, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6806 | Storage startup, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6807 | Store forward storage startup, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6848 | Good, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6858 | Good point of version Latest, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6868 | Counter rollover has occurred, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6904 | First value received in store forward mode, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6905 | Not a number, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
6908 | First value received from IOServer, timestamp overwritten; values out of time sequence, intermediate point stored by deadband storage algorithm, partial cycle |
7168 | Bad Quality of undetermined state, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7169 | No data available, tag did not exist at the time, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7170 | Running insert, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7178 | Communication loss, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7184 | Good value, received out of time sync (cyclic tag), timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7185 | Duplicate time stamp; infinite slope, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7188 | IDAS overflow recovery, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7192 | IOServer communication failed, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7212 | Pipe reconnect, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7232 | Cannot convert, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7318 | Storage startup, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7319 | Store forward storage startup, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7360 | Good, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7370 | Good point of version Latest, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7380 | Counter rollover has occurred, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7416 | First value received in store forward mode, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7417 | Not a number, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
7420 | First value received from IOServer, timestamp overwritten; server timestamping selected, intermediate point stored by deadband storage algorithm, partial cycle |
65536 | No data stored in history |