TN - 1170 Unable to switch to primary IDAS

Description

 

This article from InSource shows how to correct the error:  Unable to switch to primary IDAS

  • Author: Ron Tanner
  • Published: 06/30/2021
  • Applies to: AVEVA Historian

Details

Unable to switch to primary IDAS errors in the SMC logger for the AVEVA Historian when making configuration changes.

clipboard_e8cab238a5750247fd766fb6c4707491c.png

 

There is a known intermittent issue when IDAS gets into a deadlocked state during database reconfiguration.
When in that state all reconfiguration requests time out, including getting the configuration version call.
 

To correct the issue, delete all IDAS configuration files stored in All Users\ArchestrA\Historian\IDAS\Configurations on the same machine where the IDAS is installed.

The Configuration Service will restart IDAS within a minute and the issue will be resolved.