- Author: Brian Schneider
- Published: March 3rd, 2025
Details:
Description
This article from InSource shows...
- Author: Ernest Lee
- Published: 09/29/2016
- Applies to: InTouch 10.1 and higher
Details
When launching WindowViewer you may receive the error message: Application was developed with a Win16 version of InTouch OLDER than version 5.0.
This error indicates the file vers_res.inf is missing or corrupt. This file contains the software version information that WindowViewer checks before launching.
The fix is to create a brand new modern application and then copy the vers_res.inf file from the new application and paste it in the application folder of the non-working application.
You can find the path to the application folder by launching InTouch Application Manager.