TN - IT250211 Renaming a Managed InTouch Application

Last updated: May 15th, 2026

Description

  • Author: Brian Schneider
  • Published: May 15th, 2026

Details:

Description

When you have a managed InTouch app, you can rename the instance, but this will not rename the actual application seen in InTouch Application Manager.

Problem Description:

Have an InTouchViewApp that has been developed and now want to deploy it. When the template was first created a name was given to the application during the setup of the InTouchViewApp template, which by default is the name of the template object. When the application is deployed, this application name gets used as the display name in the InTouch Application Manager. If you rename the InTouchViewApp templates or instances and redeploy, this name change is not reflected in the InTouch Application Manager, instead it keeps the name that was originally entered when the InTouchViewApp was created.

Solution:

To rename the InTouchViewApp you will need to do this from the IDE by modifying the properties of this application. To do this:

  1. Check out the InTouchViewApp application's template by right clicking on it and selecting Check Out. (Be sure to do this on the template in the Template Toolbox, not on the instance.)
  2. Right click on the template and select Application Information.
  3. The Application Name field that is shown at the top of the Application Information window is the name of your application as it will be shown in InTouch Application Manager.
  4. Enter the name you would like to have displayed in InTouch Application Manager into this field.
  5. Right click on the template and select Check In to save the changes.
  6. Redeploy your instances to see the change in InTouch Application Manager.
changing name managed app
Give feedback about this article

Recommended articles

Setting up an Intouch 2014 R2 application to work with a Read Only license

Read More

TN 1369 How to Create a Copy of a Template With a Different Name

Read More

TN 1232 Coverting a Modern InTouch Application to Stand Alone

Read More

TN - IT - 150504 Launch a different WindowViewer application from a running WindowViewer application

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand