TN 1439 Successfully exporting data to CSV using the hist data wizard
Last updated: March 3rd, 2025Description
- Author: Kwame McDonald
- Published: March 3rd, 2025
Details:
Description
This article from InSource shows how to Successfully export CSV data using the hist data wizard
- Author: Kwame McDonald
- Published: 4/2/2024
- Applies to: Historian
Problem:
HistData wizard issue when exporting data to csv when selecting save nothing happens

Solution:
It is recommended to break the cell of the HistData wizard to see the script, You will see the action script associated with the save to file button. Historical Data Manager needs to be running to accomplish this. The location of the file is located below:
C:\Program Files (x86)\Wonderware\InTouch