TN IT330 Unable to log into InTouch Access Anywhere (Password is either expired or must be changed)
Last updated: February 27th, 2025Description
- Author: Benjamin Davis
- Published: February 27th, 2025
Details:
Description
This article from InSource shows how to resolve the error "Password is either expired or must be changed" when attempting to log into InTouch Access Anywhere
- Author: Benjamin Davis
- Published: 03/15/2019
- Applies to: InTouch Access Anywhere
Details
When attempting to open an application in InTouch Access Anywhere, you may receive this error message…
To resolve...
- Go to Windows Services.
- Locate InTouch Access Anywhere Server service.
- Stop the Service.
- Right click the service and select Properties.
- Click the Log On tab.
- Change the account from Local System to any account with administrative privileges on that machine.

- Start the Service.