Description

  • Author: Brian Schneider
  • Published: March 3rd, 2025

Details:

Description

When trying to run a Managed InTouch Application in WindowViewer, on a Terminal Server through an RDP session, you receive the error "NAD unable to download new application". 

If you look at the SMC logs, you may find that it says

"NAD could not remove directory: C:\Documents and Settings\All Users\Application Data\Archestra\ManagedApp" 

AND

"NAD could not remove file: C:\Documents and Settings\All Users\Application Data\Archestra\ManagedApp\xtagnam.$$$"

  • Author: Rufus Handsome
  • Published: 10/14/2015
  • Applies to: InTouch 10.1 and Application Server 3.1

Resolution

The resolution is to undeploy all running InTouch managed applications on the terminal server node and delete the xtagnam.$$$ file and redeploy.

download issue application problem
Give feedback about this article

Recommended articles

TN - IT250211 Renaming a Managed InTouch Application

Read More

Setting up an Intouch 2014 R2 application to work with a Read Only license

Read More

TN 1369 How to Create a Copy of a Template With a Different Name

Read More

TN 1232 Coverting a Modern InTouch Application to Stand Alone

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand