How to switch an InTouch application to "Read Only" by modifying the InTouch.ini file

Last updated: March 3rd, 2025

Description

  • Author: Joe Hefner
  • Published: March 3rd, 2025

Details:

Description

This article from InSource shows how to modify a Wonderware InTouch application ini file to make the application "Read Only". This will eliminate the need for maintaining a seperate copy of the application for "ReadOnly" machines.

  • Author: Joseph Hefner
  • Published: 06/08/2016
  • Applies to: Intouch 2014 R2 and later

Details

Note: The tech note describes an approach that is useful but not officially supported. Make sure to backup all InTouch applications before following the instructions below.

  1. After deploying the application, navigate to the location from the screenshot below on the client that you wish to run the "ReadOnly" application on.
    Replace "Demo1-AlarmDemo" with the name of your Intouch application:
  2. Locate the InTouch.ini file in the application folder and right click on it and choose edit.
  3. Add the following feature line to the bottom on the Intouch.ini file as in the screenshot below:
    MarkAppReadOnly=1
  4. Save the modified Intouch.ini file to a seperate location:
  5. Right click on the saved Intouch.ini file and choose "Copy".
  6. Paste it into the application directory:
  7. Choose "Replace the file in the destination".
  8. If you have previously launched WindowViewer from the user account you may need to also make the change to the InTouch.ini file at the location below:
    Replace Administrator with the User account in question:

 

disable modify
Give feedback about this article

Recommended articles

TN - IT250211 Renaming a Managed InTouch Application

Read More

Setting up an Intouch 2014 R2 application to work with a Read Only license

Read More

TN 1369 How to Create a Copy of a Template With a Different Name

Read More

TN 1232 Coverting a Modern InTouch Application to Stand Alone

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand