Embedded client control is missing on remote deployed application

Last updated: March 5th, 2025

Description

  • Author: Brian Schneider
  • Published: March 5th, 2025

Details:

Problem:

An embedded client control that was imported through the IDE exists works fine when WindowViewer is launched from the IDE machine but when the application gets deployed to a remote machine the graphic shows up as a RedX and a message says “Client Control not found” as below:

Resolution:

Manually copy the Client Control from the following directory on the IDE machine to the corresponding directory on the remote client machine:

32 Bit System

C:\Program Files\ArchestrA\Framework\Bin

64 Bit System

or C:\Program Files (x86)\ArchestrA\Framework\Bin

In the example below you would copy the entire folder Invensys_Systems__Inc__aaHistClientTrendControl.dll which is the name of the embedded control over to the remote client machine:

 

client control missing
Give feedback about this article

Recommended articles

TN - IT250211 Renaming a Managed InTouch Application

Read More

Setting up an Intouch 2014 R2 application to work with a Read Only license

Read More

TN 1369 How to Create a Copy of a Template With a Different Name

Read More

TN 1232 Coverting a Modern InTouch Application to Stand Alone

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand