TN 1302 Historian - Disabling Indexing For Debugging Purposes

Last updated: March 3rd, 2025

Description

  • Author: Frank Ross
  • Published: March 3rd, 2025

Details:

Description

This article from InSource shows how to disable indexing within the Aveva Historian to validate tag data is making it to the historian.

  • Author: Frank Ross
  • Published: 12/09/2022
  • Applies to: Aveva Historian 2017 & Newer

Details

Scenario: Customer has identified specific tags which do not appear to be historizing within the Aveva Historian. However, other tags are successfully being historized. The configuration between those that are not and those that are historizing are the same. Further analysis shows that if new tags are created using the same PLC references, those tags are historizing too. The root cause could be from an indexing issue, so to prove this theory, the system needs to have indexing disabled. Once disabled, the Historian client (or by using SQL queries), can be used to verify the tag data is actually making it to the Historian and being stored in the data blocks. 

To disable indexing on the Historian node, you will need to make a change to the Registry. Before making any changes to the Registry, it is recommended to make a copy of the Registry. 

The Registry setting that needs modified is to add a new entry Dword 32 to HKLM>Software>Archestra>Historian>Programs>aahStorage, name it UseIndexing and set it to 0. (see example below). 

Once the Registry setting has been modified, you can use either the Query Tool or Trend to verify the "missing" tag data is now appearing within the queries.

Please note: This registry change should not be a permanent change because it disables indexing, thus making the queries very ineffecient. What this essentially proves is that there is a potential indexing issue but the tag data is making it into the Historian data blocks.

 

historian debugging
Give feedback about this article

Recommended articles

TN 1394 Error when Deploying: Remote Node's UserID/Password don't match GR Node's

Read More

TN 1321 Unable to activate license with message "Unable to communicate with the Activation Server." For only one license serial number.

Read More

TN 1298 DCOM Harding PowerShell Script

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand