TN 1223 Re-Connecting to System Management Server after Hardware Replacement or VM Restoration

Last updated: March 6th, 2025

Description

  • Author: Mario Meza
  • Published: March 6th, 2025

Details:

Description

This article from InSource will guide you through reconnecting to System Management Server (SMS) after a hardware replacement or VM restoration.

  • Author: Mario Meza
  • Published: 03/09/2022
  • Applies to: System Management Server 2017 and above

Guide listings

template('MindTouch/IDF3/Views/Guide');

If you connect a machine to the System Management Server (SMS) and then later replace the machine due to hardware failure, or restore the VM to a state prior to that connection without first disconnecting the machine from the System Management Server (SMS), you will not be able to reconnect that same machine to the System Management Server (SMS). This is to protect the security of the system. System Management Server (SMS) uniquely identifies each machine that connects to it. Should an intruder attempt to pretend to be that machine (spoofing) and re-registers with that machine’s name, the System Management Server (SMS) will detect the mismatched identity and reject the suspected intruder’s registration.

Resolution:

  • Before replacing a connected machine, and/or restoring the connected VM to a pre-connected state, run the Configurator on that machine and disconnect it from the System Management Server.
  • If that is not possible (i.e., the machine is no longer available due to hardware failure), then you will need to remove the connection information on the System Management Server (SMS) manually:

After attempting to reconnect the machine, the logger will contain the warning:

“ArchestrA.CertificateManager: Please un-register the device <device name> from management server. Use the (Remove-AsbDevice) script to remove the device registration”

Remove-AsbDevice is a PowerShell command that will remove the machine’s connection information from the System Management Server (SMS). 

To execute this script on the System Management Server (SMS) node launch PowerShell as Administrator and enter Get-AsbDevice 

You will be prompted to enter the Management Server Address which should be entered in the following format

https://<SMSHOSTNAME>:443

* Be sure to use all CAPS for the SMSHOSTNAME

Once entered you will see a Windows PowerShell Dialog credential request (below).

Enter the user name and password of a local Administrator and select OK

In a moment you should see the interface populate with a list of registered devices

Once you've identified the DeviceID of the machine or VM that no longer exists, enter Remove-AsbDevice and hit enter.

You will be prompted to enter a DeviceID. Enter the DeviceID of the machine or VM you want to remove and hit enter.

You will again be prompted to enter the Management Server Address which should be entered in the following format:

https://<SMSHOSTNAME>:443

* Be sure to use all CAPS for the DEVICEID and the SMSHOSTNAME

Once entered you will again see the Windows PowerShell Dialog credential request.

Enter the user name and password of a local Administrator and select OK.

From here you can re-run Get-AsbDevice to validate the DeviceID no longer exists in the list of registered devices or you can go straight to configure the system management server from replacement system configurator

 

reconnect restore
Give feedback about this article

Recommended articles

TN 1026 wwClient Unable to Load Connections

Read More

TN 1438 How to check if a Hotfix is installed

Read More

How to ping and get a ipv4 address returned instead of ipv6

Read More

OPC Quality and Quality Detail Codes

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand