Details:

Description

This article from InSource shows one way how to deal with the Batch Manager crashing after migrating from a Physical to a Virtual Machine.

  • Author: Rufus Handsome
  • Published: 04/26/2017
  • Applies to: InBatch v8.1

Details

After migrating from a physical computer to a virtual machine, when starting up the VM, everything starts up fine. However, when going to the client to initialize a batch in batch manager, the service suddenly stops and you receive the message similar to "unexpected error, warm restart c461 - shutdown - disconnected from batch manager." With this situation, It would appear that the hidden .BatchWR directory is missing from the "C:\Program Files\FactorySuite\InBatch\cfg\config_A\" folder. 

To resolve the issue, open a dos window with cmd, then navigate to the directory "C:\Program Files\FactorySuite\InBatch\cfg\config_A", then use the "mkdir" command as follows: "mkdir .BatchWR", to re-create the hidden directory. Then in InBatch Scheduler, run a batch to test and verify.

resolve crashes virtual migration
Give feedback about this article

Recommended articles

TN IB001 Configuring InBatch Remote Development Client

Read More

TN IB001 How to import Recipes into InBatch from an XML file

Read More

TN IB001 How to turn on Security in InBatch 2012 R2

Read More

TN IB002 Create Batch Scheduler in InTouch Using InBatch ActiveX Objects

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand