Description  

This article from InSource walks through setting up additional log flags in the OCMC log viewer. This can be helpful when troubleshooting deployment failures, if the default logs are not providing enough information.

 

Solution Steps:

  1.  Right click on the log viewer that you are applying the additional log flags on and select “Log Flags”

2.  Add the recommended component and additional flags:

        

3.   Apply the additional log flags by clicking  “File \ Apply” on the menu.                          

 

4.  Attempt to deploy with additional log flags added.

 

Important note:  Always remove the additional log flags once troubleshooting has completed. 

 

Below is the recommended list of log flags that can be turned on for the GR node and the remote node:

 

On the GR node:

Component Log Flags
aaBootstrap BootstrapRegister, CPlatformMapping
aaDCOMTransport Trace
DComInterfaceAccess Trace, BootstrapTrace
PlatformCategory Trace, PlatformCategory
WWPackageServer MultiThreadedDeploy, DeployProgress, LogAllFailures
WWPackageManager Trace, LogAllFailures
FileCopyService Trace
aaPIM PimTraceOn

 

On the remote node:

Component Log Flags
aaBootstrap BootstrapRegister, PlatformMapping, FileVersion
aaDCOMTransport Trace
aaPIM PimTraceOn, PimTraceWarnErrorOn, FileRefCount, MsiDiagnostics
DComInterfaceAccess BootstrapTrace, Trace
FileCopyService Trace

 

_____________________________________________________________________________________________________

deployment troubleshooting
Give feedback about this article

Recommended articles

TN AppSvr325 Check-list For Troubleshooting Failed Deployment Attempts on Industrial Application Server version 2017 Update 3

Read More

[ISS Support Case] App Server - Deployment

I think this may be a networking/IT issues just reaching out this way to confirm that with you. This warning has been going on for a while as it looks to have started last year in April. Didnt realize that at the time since it still worked just noticed it after trying to deploy a change of the ViewApp that was made. Failed to get file repository path. Failed to create bootstrap on remote machine.

Read More

[ISS Support Case] Platform failed to deploy

Failed to create bootstrap.

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand