[ISS Support Case] DB Dump Fails in IDE with COMException and File Lock Errors
Last updated: October 17th, 2025Description
The customer reported that when performing a DB dump of selected objects from within the AVEVA IDE (2017 Update 3), the operation fails with the following errors: COMException Error OLE_E_NOSTORAGE Exception in DumpTemplateInstance() function : System.Runtime.InteropServices.COMException (0x80040012): Not able to perform the operation because object is not given storage yet (Exception from HRESULT: 0x80040012 (OLE_E_NOSTORAGE)) at ArchestrA.Core.MxValueClass.GetCustomStructVB(Int32& pGuid, Byte[]& pStruct) at ArchestrA.Configuration.GRDumpLoadServer.DumpTemplate.DumpTemplateInstances() File Lock Error tmp file in use Exception in function ProcessThreadResultAndDumpToFinalFile The process cannot access the file 'C:\Program Files (x86)\ArchestrA\Framework\Bin\Temp\tmp6C02.tmp' because it is being used by another process. Root Cause: The OLE_E_NOSTORAGE error is caused by one or more objects in the IDE that have not been validated or saved, and therefore do not have storage assigned in the Galaxy repository. The file lock error is the result of another process (such as antivirus software or a second IDE instance) locking the temporary dump file during export.
- Author: Kevin Modlin
- Published: October 17th, 2025
Details:
| Product: Application Server |
| Version: 2017 |
| Solution: [Solution is visible below when you're logged in and have a current subscription] |
| Date Created: | 05/13/2025 |
| Case: | 97914 |
Recommended articles
[ISS Support Case] Synchronize Views is not working correctly in the IDE
Read More[ISS Support Case] Historian Data Gap On Appengine Failover In SP Version 2023 R2 P1
I am seeing an issue with SP2023 R2 P1 related to appengine failovers. When I cause an appengine failover, data (primarily analog) has a gap in the trend until the data changes. Sometimes the gap stays but sometimes the gap is "filled" in for some reason. I'm having a bit of a consistency issue trying to replicate this problem. Every time I cause a failover, the results are slightly different but I do see bad results. To demonstrate this, I created two videos to show what I'm seeing. If someone can create a problem ticket and reach out to me, I can forward the videos to InSource to show what I'm seeing.
Read More[ISS Support Case] MQTT setup crashes OCMC
MQTT server - CDP 2023 check encryption/validate security - no issue port validates enable user identity/try to bring certs in shuts down OCMC nothing in OCMC logs event viewer shows an app crash for mmc with cfg_mqtt_plctype1.dll as the faulting module advised repair after conferring with aveva - called client to discuss and confirm New SR960455477 (requesting) Log file Config Files Do Not upgrade Stay @ the same version of CDP Call in on 9/12/2024 No success on the MQTT server with the antivirus turned off, and it was even worse this time. Could not hook to AWS server. Proceeded to step 2, entered certificate in case it needed to log in to AWS server, but the OCMC shut down. Restarted OCMC acted strange, restarted computer. OCMC behaved normally after, but still no success with MQTT. Wants a call back whenever you're available, doesn't have to be tonight. CDP shows 2023
Read More