Skip to main content
InSource Solutions

TN WW165 Firewall ports for Wonderware products

Description

 

One of the primary ways to protect your critical infrastructure is through the use of firewalls. Whether we are discussing hardware or software firewalls, the important thing of note is which ports need to be open and in which direction. This article from InSource shows the firewall ports that need to be open for various Wonderware products. However, this list is not comprehensive and the customer should always refer to the product documentation for an individual product.

 

  • Author: Mike Viteri
  • Published: 9/2/2016
  • Applies to: Wonderware

Details

 

 

Application Server

DCOM 135/tcp
File and printer sharing445/tcp
SQL TCP 1433/tcp
SQL Server Browser 1434/udp

 

DA Servers

DAS SI Direct 102
DAS MBTCP 502
DAS ABTCP 2221
DAS ABTCP 2222
DAS ABTCP 2223
DAS ABCIP 44818
 

Historian


File and printer sharing 445/tcp
SQL Server Browser 1434/udp
SQL TCP 1433/tcp
DCOM 135/tcp

 

InBatch


Vista 9001/tcp
EnvMngr 9002/tcp
MsgMngr 9003/tcp
SecMngr 9004/tcp
RedMngr 9006/tcp
UnilinkMngr 9007/tcp
BatchMngr 9008/tcp
LogMngr 9011/tcp
InfoMngr 9012/tcp
RedMngrX 9013/udp
RedMngrX2 9014/udp
HistQMngr 9015/tcp
HistQReader 9016/tcp

 

Historian Client


License Server 27000-27009
SQL 1433

 

Information Server


HTTP 80
SSL 443

 

SuiteLink


Suitelink 5413