Skip to main content
InSource Solutions

Microsoft Updates KB4056890, KB4056892, KB4056895, KB4056898 and KB4056899 causing instability on computers with Schneider Electric software installed

,@api,deki,files,5466,TA287.pdf

Description

 

This article describes Schneider Electric Tech Alert 287

  • Author: Joseph Hefner
  • Updated: 02/09/2018
  • Applies to: All versions of Wonderware software

Details

Microsoft has released a set of updates for “Meltdown and Spectre vulnerabilities”. These updates have an issue that is causing Wonderware Historian to fail. There are also reports of it causing a variety of problems related to Device Integration and Application Server deployments.

Schneider Electric highly recommended these Updates not be applied to systems running their products. Below is the latest list of updates that are known to cause instability issues.

 

KB4056896, KB4056890, KB4056892, KB4056895, KB4056898 and KB4056899

 

Since that time, Schneider Electric has successfully tested Microsoft's recently-released KB4057401, KB4057402, KB4057142 and KB4073291, and have confirmed they resolve the instability issues reported in this Tech Alert.

 

Schneider Electric has updated Tech Alert 287, which further explains the issue and has updated the recommendations if one of the Microsoft updates have been installed.  Please review the Tech Alert below for more details.

https://softwaresupportsp.schneider-electric.com/Pages/OKMArticleResult.aspx?docId=TA287

 

Tech Alert 287 is also attached to this article.