TN IT228 Using NAD with a Modern Application

Last updated: March 6th, 2025

Description

  • Author: Rich Brooks
  • Published: March 6th, 2025

Details:

Description

This article from InSource shows how to configure NAD with a Wonderware InTouch Modern application type.

  • Author: Rich Brooks
  • Published: 9/28/2016
  • Applies to: InTouch 2014R2 P1 & SP1

Details

Network Application Development (NAD) allows changes from the WindowMaker (Development Server) to be pushed out to the WindowViewer (Runtime Node). The steps to initially push out changes are listed below. These steps have changed slightly with the latest releases of the software.

Note: Not following the steps as listed below may result in white rectangle placeholders on windows where ArchestrA graphics should be.

Step 1: Share the master InTouch application directory. Use an URL path such as \\<servername>\<share name>\<project folder>

Step 2: Notify Clients from the WindowMaker

Step 3: Setup NAD and launch WindowViewer

Step 4: Make a change to the master application and save the changes

Step 5: Notify Clients from the WindowMaker (repeat of Step 2)

Step 6: Click yes to receive the update on the client

 

nad integration modern app
Give feedback about this article

Recommended articles

TN - 1240 Creating a Watchlist Using an Import File

Read More

How to receive group emails

Read More

TN 1242 Aveva Historian Storage Locations and Best Practices

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand