Some content on this site is available only to logged-in subscribers. Contact Us for information on becoming a subscriber.

InSource.Solutions | InSource Training | InSource Client Portal
InSource Solutions Logo
Log In Sign Up
InSource.Solutions InSource Training InSource Client Portal Log In Sign Up
  • Home
  • AVEVA Edge
  • AVEVA Edge Tech Notes

TN ITME111 Configuring Scaling for ADAM Modules and InTouch ME

Last updated: February 28th, 2025

Description

  • Author: Rich Brooks
  • Published: February 28th, 2025

Details:

Description

This article from InSource shows how to configure scaling from Advantech ADAM modules to Wonderware InTouch Machine Edition.

  • Author: Rich Brooks
  • Published: 3/16/2017
  • Applies to: InTouch ME v8.0 and higher

Details

An example is provided to demonstrate scaling for the ADAM 6018 Module. The 6018 is an eight channel isolated thermocouple input Modbus TCP module. Two of the inputs are configured in this example. The input range for both of these thermocouples is 0 to 760 degrees Celsius. These are configure on channels 0 and 1 below.

InTouch ME reads the Modbus (Current) value. This is a 16-bit value decimal value ranging from 0 to 65,535. The decimal value is scaled to Celsius in InTouch ME as shown below.

Both of the decimal value inputs are divided by 86.230263. The raw range is 0 to 65,535 and the engineered range is 0 to 760. Divide the raw range by the engineered range to calculate the divisor as circled above.

65,535 - 0 / 720 - 0 = 86.230263

The temperature values in the HMI are then scaled to Celsius for the runtime display.

scaling configuration module setup
Give feedback about this article

Recommended articles

TN 1393 Deleting Tags from AVEVA Insight

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand