TN DAS153 Connecting to an OPC UA Server through the Wonderware Gateway OI Server

Last updated: April 3rd, 2025

Description

  • Author: Joe Hefner
  • Published: April 3rd, 2025

Details:

fDescription

This article from InSource walks through setting up a connection to an OPC UA Server through the Wonderware Gateway OI Server.

  • Author: Joseph Hefner
  • Published: 12/6/2016
  • Applies to: Wonderware Gateway OI Server 1.0 or later

Details

Step 1) Right click the Configuration and choose "Add OPCUA Connection":

Step 2) Right click on the new OPC Object and select Rename.

In this case I have renamed the object to OPC.

Step 3) Enter the OPC UA Server Information:

Step 4) Right click on the OPC Object and select "Add OPCUAGroup Connection":

Step 5 ) Rename the new OPCUA Group by right clicking on it and selecting "Rename":

In this example, I have renamed it to Group:

The Device Group Name below will be used as a topic when connecting to the Gateway OI Server.

Step 6) Right click on the Gateway OI Server and choose "Activate":

Step 7) Test the connection.

In the example below, I am using Wonderware client to test the connection to the OPC UA Server:

First go to Connections \ Create:

Enter the node name for this computer, “gateway” for the Application name, and the Device Group Name from Step 5 will be your Topic:

Finally, Go on the Item Menu. In the Item box enter the name of the OPC UA Item you would like to read and click the "AdviseEx" button:

If you have established good communication the quality of the item you are reading will be 0x00c0 as below:

 

opc ua wonderware gateway
Give feedback about this article

Recommended articles

How to receive group emails

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand