TN - DR - 25091705 Dream Reports Generating as N/A

Last updated: May 18th, 2026

Description

  • Author: James Rochester
  • Published: May 18th, 2026

Details:

  • Author: James Rochester
  • Published: 9/17/2025
  • Applies to: Dream Reports 4.83 and above

Description

In an instance where you generate a report and the report is void of information or displays N/A this indicates that your user account may lack sufficient permissions to the SQL Database or that you may have been disconnected from the database.

Runtime manager errors: In some cases, the Dream Report Runtime Manager may stop working correctly.  

Connection timeout: A common issue occurs with databases like MySQL, which have a default connection timeout. If Dream Report doesn't re-establish the connection, reports will start showing "N/A" after a few hours.

Begin by Restarting the restarting the RTM Reporting System Runtime Manager and then generate a new report to test if it is still showing as N/A.

Insufficient permissions: The account running the Dream Report Runtime Engine may not have the necessary access rights to read data from the connected data source, causing values to appear as "N/A" in reports. 

An example of account that would have sufficient rights would be an Administrative account that exist as a Historian Administrator or in the SQL login system. This is specific to Dream Reports with the Historian database as the data source, but the same principles apply to PI, Reports for Operations or Plant Scada data sources.

Solution:

  1. Navigate to the Windows Services console.
  2. Locate the "RTM Reporting System Runtime Manager" service.
  3. Open its properties and navigate to the Log On tab.
  4. Instead of using the default local system account, select "This account" and provide the credentials of a Windows user account with sufficient administrative privileges to the SQL/Historian Server or your preferred data source. 

 

 

unavailabe dream logs
Give feedback about this article

Recommended articles

[ISS Support Case] Dream Reports Customize Web Portal Reports List

I'm running a couple of Windows schedule tasks to close and open Chrome every hour and refresh a report that is being displayed on a customer screen. This is working fine but when the report opens it has the report browsing list on the left side as a default so the report is cut off. Is there a way to not have that menu list opened as a default on the web reports? Please see attached screenshots.

Read More

[ISS Support Case] Display InTouch Tags In Dream Report As a Widget

Working with Dream Reports more familiar with InTouch. Is it possible to import screens from InTouch to Dream Reports? objective: create a 'dashboard' with widgets and make tables like a flow chart like a hybrid between DR and InTouch. Possible to have a widget that updates at a defined interval? Data Source: InTouch Tag: Live Analog Value Dynamically Update?

Read More

[ISS Support Case] Historian Data Importer Failure

Client reached out as when attempting to import any CSV data into the Historian data importer it fails with the same error message: "Error processing the file. Error in line number 2. Unsupported delimiter." This was tested with multiple unique CSV's exported from both Query and Trend.

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand