Description

  • Author: Brian Schneider
  • Published: March 11th, 2025

Details:

Description

Article describes ways to filter the MES Utilization Control. 

  • Author: Michael Walker
  • Published: 09/25/2014
  • Applies to: Wonderware System Platform 2014 R2, MES 2014

Details

The MES Utilization Control shows DT Reason for the MES Database. The list of these reasons can be filtered by Time, State and Event Count using the controls methods and properties. The items below provide examples of this.

The UtilizationFilter.UtilStatusFilter property determines what state filter , if any, will be performed based on utilization status(that is, Time and Down Time). The UtilStatusFilter property is enumerated as seen below:

 {Runtime=0,
Downtime=1,
Neither=2,
All=3}

The UtilizationFilter.UtilTimeFilterType property determines what time based filtering, if any, will be on the data. The UtilTimeFilterType property is enumerated as seen below:

{LastNEvents = 0
ThisShift = 1
LastShift = 2
ThisHour = 3
LastNHours = 4
CurrentDay = 5
Yesterday = 6
CurrentWeek = 7
LastWeek = 8
CurrentMonth = 9
LastMonth = 10
Custom = 11
None = 12}

The UtilizationFilter.UtilFilterUnAck property specifies whether unacknowledged events, acknowledged events, or both types of events be shown. The UtilFilterUnAck property is enumerated as seen below:

{Unacknowledged = 0,
Acknowledged=1
, Both=2}

time filters utilization control
Give feedback about this article

Recommended articles

How to receive group emails

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand