TN WW179 Alarm Logger " Error: Unable to create database"

Last updated: March 6th, 2025

Description

  • Author: Michael Viteri
  • Published: March 6th, 2025

Details:

Description

When trying to recreate the WWALMDB. You get " Error: Unable to create database". This reason this happens is because the WWALMDB.mdf and WWALMDB.ldf are still in the SQL data folder.

  • Author: Mike Viteri
  • Published: 6/24/2017
  • Applies to: Intouch 7.11 and greater

Details

  1. Go to the install drive of the SQL Server. Find the MSSQL\Data folder
  2. You should find the WWALMDB and WWALMDB_log. You can cut them out of the "DATA" folder. Put them somewhere safe in case you need them for later. Close the window.
  3. Open up the Alarm DB Logger Manager. Click Settings.
  4. Enter your information then click create build the database. You will see Created Database depending if you choose Detailed or Consolidated.
  5. Reconfigure the rest of the setting then you can start the Alarm DB Logger.
database creation alarm log
Give feedback about this article

Recommended articles

How to receive group emails

Read More

Aveva Diagnostic Utility wwClient

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand