Details:

Description

This article from InSource Solutions shows you how to set up a local InTouch I/O tag to read a tag in a remote InTouch application.

  • Author: Daniel London
  • Published: 03/02/2017
  • Applies to: InTouch

Details

It is possible to reference a tag in a remote application (one running on another computer) inside of a local InTouch application on a different machine. To do so, you will first have to set up an access name to the WindowViewer session on the remote machine. The second part involves creating an I/O tag in the local application that references the tag you are trying to read in the remote application.

NOTE: WindowViewer must be running the application on the remote machine for the live value to update.

  1. In the local application set up a new access name following the example below.

Node Name: <Host Name / IP of remote machine>

Application Name: VIEW

Topic Name: tagname

  1. In the local application create a new I/O tag in the Tagname Dictionary that references the InTouch tag on the remote system/application.

Access Name: Access name you mapped to the remote InTouch application.

Item: Tag name of the tag in the remote InTouch application.

 

remote setup local i/o
Give feedback about this article

Recommended articles

TN 1393 Deleting Tags from AVEVA Insight

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand