TN AG113 Building a Trend and Alarm Symbol - Part 2 - Adding DateTime Selection

Last updated: March 7th, 2025

Description

  • Author: Brian Schneider
  • Published: March 7th, 2025

Details:

Description

In this series we will create an ArchestrA Symbol which shows us Trend and Alarm information correlating the two sets of data with one another. In this second article we will add the ability to customize the time and date range that we are viewing.
 

  • Author: Dillon Perera
  • Published: 12/30/2015
  • Applies to: InTouch 2014R2

This article is the second in a series:

Part 1: TN AG112 Building a Trend and Alarm Symbol - Part 1 - Linking the Data

Part 2: TN AG113 Building a Trend and Alarm Symbol - Part 2 - Adding DateTime Selection

Details

Note: Before beginning, you may want to create a backup of your symbol or application.

  1. Open the TrendAndAlarmDisplay Symbol for editing, which we created in the Part1 article.
  2. From the Tools, select the DateTimePicker and add it underneath the AlarmClient1 control, and name this element dtStartTime from the properties window. 
  3. Duplicate the dtStartTime element and name the new copy dtEndTime and place it below dtStartTime.
  4. Add labels beside each DateTimePicker.
  5. Add a Custom Property called DefaultEndTime, of type Time. This will be a Private property, with a Tag value set to Now(). This will be used to automatically set the End Time DateTimePicker to the current time.
  6. Add a Custom Property called DefaultStartTime, of type Time. This will be a Private property, with a Tag value set to DefaultEndTime.Add(-5). This will be used to automatically set the Start Time DateTimePicker to the current time - 5 minutes.
  7. Double click on the dtEndTime DateTimePicker, and in the Time Reference set this equal to DefaultEndTime. In the Configuration Section set the Format to Custom, with a value of "MM/dd/yyyy h:mm tt". Click OK.
  8. Double click on the dtStartTime DateTimePicker, and in the Time Reference set this equal to DefaultStartTime. In the Configuration Section set the Format to Custom, with a value of "MM/dd/yyyy h:mm tt"
  9. Add a button beside the DateTimePickers that says Update To Selected Time.
  10. Double click on the button and add an Action Script animation. Enter the following script:

    'Update the AlarmClient1 control to use the selected times
    AlarmClient1.TimeSelector.SetStartAndEndTimes(dtStartTime.Value.ToString, dtEndTime.Value.ToString, 0);
    AlarmClient1.Requery();

    'Update the TrendClient1 control to use the selected times
    TrendClient1.SetStartAndEndTimes(dtStartTime.Value, dtEndTime.Value,0);

  11. Double click on the AlarmClient1 control, and on the Alarm Mode configuration uncheck the Update to Current Time option.
  12. Go to the Event configuration and reopen the Double Click script. Add the following lines to the end of the script:

    'Update the TrendClient1 control to use the selected times
    TrendClient1.SetStartAndEndTimes(dtStartTime.Value, dtEndTime.Value,0);

  13. Save your work, and test in Runtime. You should now be able to select a specific Start and End time, then click the Update button to only show alarms from that time period. If you double click on one of those alarms you will then see the trend information for that same period.

 

datetime selection symbol customization
Give feedback about this article

Recommended articles

TN 1398 Determining Active Communications Server

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand