TN AG112 Building a Trend and Alarm Symbol - Part 1 - Linking the Data

Last updated: March 7th, 2025

Description

  • Author: Brian Schneider
  • Published: March 7th, 2025

Details:

Description

In this series of articles from InSource we will create a Wonderware ArchestrA Symbol which shows us Trend and Alarm information correlating the two sets of data with one another. In this first article we'll begin by creating a symbol which simply shows the Trends and Alarms at the same time, allowing us to double click on an alarm and bring up that tag in Trend.

  • Author: Dillon Perera
  • Published: 12/30/2015
  • Applies to: InTouch 2014R2

This article is the first in a series:

Part 1: TN AG112 Building a Trend and Alarm Symbol - Part 1 - Linking the Data

Part 2: TN AG113 Building a Trend and Alarm Symbol - Part 2 - Adding DateTime Selection

Details

  1. To begin, create a new ArchestrA symbol in the Graphic Toolbox called TrendAndAlarmDisplay. Then open this symbol for editing.
  2. From the Embed Graphic icon add the TrendClient and AlarmClient to your Symbol.
  3. Double click on the TrendClient1 control and go to the Historical Sources Configuration. Enter in the connection information for your Historian. Note, in this case my Historical Source is given the name "LOCALHOST".

    On the Appearance configuration, unselect the Allow highlight pen option.

    Click OK.
  4. Double click on the AlarmClient1 control and go to the Alarm Mode configuration. Set your Client Mode to Historical Alarms, and point to your Alarm Database. 

    In the Other Settings, set the time range to 5 minutes, and select Update to Current Time.
  5. Create a Custom Property called SelectedAlarmTag of type String, and make this Private.
  6. Double click on the AlarmClient1 control and go to the Event configuration screen. Select the Double Click event. Enter the following script:
'Get the tagname of the currently selected Alarm.
'This will grab the value in the "Name" column.
SelectedAlarmTag = GetSelectedItem("Name");

'Clear all the pens in the TrendClient1 display so we only see one tag.
TrendClient1.ClearPens();

'Add the selected pen to the TrendClient1 display
'The InTouch: will tell it to grab any new/live data directly from InTouch
TrendClient1.AddPen(SelectedAlarmTag,"InTouch:"+SelectedAlarmTag,"Localhost",SelectedAlarmTag,1);

'Scale the display appropriately.
TrendClient1.ScaleAutoAllPens();

  1. Once completed save your symbol, and add it to an InTouch Window. Now when you display this Window you will be shown the last 5 minutes of Alarms that have occurred. When you double click on one of these alarms the trend screen will update to show you that tag's history over the last 5 minutes.

 

data linkage trend creation
Give feedback about this article

Recommended articles

How to receive group emails

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand