TN - IT - 25092609 Projects disappear in Application Manager

Last updated: May 18th, 2026

Description

  • Author: Jamie Jackson
  • Published: May 18th, 2026

Details:

Description

This article from InSource shows how to use resolve an issue where your projects disappear from the application manager

  • Author: Jamie Jackson
  • Published: 09/26/2025
  • Applies to: AVEVA InTouch

Details

  1. Close InTouch Application Manager
  2. Navigate to C:\ProgramData\Wonderware\InTouch (if you're installation is not on the C drive, replace C with that drive)
  3. Back up and delete APPLIST.INI
  4. Launch InTouch Application Manager again
  5. If this doesn't resolve the issue, or it reoccurs, you likely have an intouch.ini file with multiple ScaleForResolution entries.
  6. For standalone InTouch, 
    1. Close InTouch Application Manager
    2. Navigate to your project folder 
    3. Open the intouch.ini file and remove any duplicate ScaleForResolution entries
    4. Launch Application Manager
  7. For a managed InTouch Application using a galaxy
    1. Close InTouch Application Manager
    2. Navigate to C:\Program Files (x86)\ArchestrA\Framework\FileRepository\<galaxy name>\ObjectFileStorage\<object name>
    3. Inside this folder there are three folders (CheckedIn, CheckedOut, DeployedXXXXX) to check the intouch.ini file
    4. Open each intouch.ini file and remove any duplicate ScaleForResolution entries
    5. Disconnect from the InTouch node
    6. Undeploy/redeploy the view app
    7. Launch Application Manager

 

 

vanishing projects missing projects
Give feedback about this article

Recommended articles

[ISS Support Case] A deployed View Application is Not Listed In Application Manager

Issue 1: Ref case 84450, platform and engines deployed successfully in IDE, however on the client workstation no applications are found. Issue 2: Launching view directly say no programs found.

Read More

[ISS Support Case] InTouch License Acquisition Failure

Client reached out due to receiving failure to acquire license when attempting to start WindowViewer.

Read More

[ISS Support Case] InTouch License Acquisition Failure

Client reached out as when user was attempting to start InTouch they were receiving a license acquisition failure message.

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand