How to use the Historian Client Active Data Grid Control Inside Intouch

Last updated: February 27th, 2025

Description

  • Author: Michael Viteri
  • Published: February 27th, 2025

Details:

Description

Use the Historian Client Active Data Grid Active X to display query data on an Intouch window.

  • Author: Mike Viteri
  • Published: 12/18/2014
  • Applies to: Historan Client & Intouch

How and When to Use this Guide

When you would like to display query data on an Intouch window.

Instructions

You will need to make sure you have Historian Client installed. This will allow the Active X control to be expose to Intouch.

  1. Open Windowmaker and Go to Special->Configure->Wizard/Active X controls.
  2. Then from the bottom window select aahHistClientActiveDataGrid Control. Once its selected then click install on the right hand side of the screen. This will then move the control up into the "installed Active X controls". Then close out.
  3. Now go into the Intouch wizard hat and select  the aaHistClientActiveDatatGrid controls.
  4. Drag this control over the Intouch window. Also create a button next to the control.
  5. Double click on the button and select touch push button->action script. Then you will select insert from the file menu then select ActiveX
  6. Next you will select methods from the Active X Control. They are Servername,Username and Password.

    Enter your Servername, Username and Password. This will allow logon to the Historian. Save and go into Windowviewer
  7. Once in Windowviewer you can click the button you created. This will allow you to logon to your Historian. Then right click on your control and select SQL.
  8. On the Active Data Grid Properties select template.(You can also insert your customer query)
  9. Select the template you want to use. Here we are using Analog History. Press select.
  10. This will paste the query in SQL tab of the control. Hit ok.
  11. Now your data should appear.

Confirmation of Success

Data is returned in your Intouch window.

active grid historian client
Give feedback about this article

Recommended articles

TN 1242 Aveva Historian Storage Locations and Best Practices

Read More

TN 1398 Determining Active Communications Server

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand