TN - Hist1498 Error in Trend Control Client: You have reached the maximum tag limit of 30

Last updated: March 18th, 2026

Description

  • Author: Ernest Lee
  • Published: March 18th, 2026

Details:

From Historian 2023, users may encounter a blocking error when attempting to add tags to the Trend Control Client. Specifically, while adding more than 30 tags, the following error popup appears:

HistClientReplicated.png

The restriction to 30 tags was intentionally implemented in the Historian Client 2023 R2 version. This change was introduced to restrict the performance impact of generating and executing complex SQL queries for large numbers of tags in the backend simultaneously.

Resolution:

This behavior was reviewed and subsequently reverted to the previous unlimited behavior in the following update:

  • Historian Client 2023-R2-SP1-Patch01 and onward
Give feedback about this article

Recommended articles

[ISS Support Case] Deployed Application Exceeding tag count

Trying to deploy a new application (was standalone now managed). Deployed successfully however(on start) getting exceeded tag db message deployed this application - platform (lots of problems) worked with an ISS resource - Deployed intouch old standalone machine has 60k license (.lic) license has not been upgraded XML license is activated either offline or online .bin license file path is : C:\ProgramData\Schneider Electric\Licensing\TrialLicensePool

Read More

[ISS Support Case] Not getting any trend data

The client is moving an application to a new PC and not getting trend data.

Read More

[ISS Support Case] Alarms disappear

The intouch alarm provider disconnected after relaunching Window viewer the alarm display again. Alarms being displayed in the alarm object Almger error: The intouch alarm provider disconnected

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand