TN - HistCl0329001 Trend Client is Missing Data that is Available in Historian

Last updated: March 23rd, 2026

Description

  • Author: Ernest Lee
  • Published: March 23rd, 2026

Details:

Everything looks fine in Historian but Trend will show gaps like the screenshot below.

 

The fix below is recommended to resolve this issue.

Please try the following:

 

  • Shutdown/Disable Historian
  • Run REGEDIT,
  • go to HKEY_LOCAL_MACHINE\SOFTWARE\ArchestrA\Historian\Programs\aahStorage
  • Create DWORD value UseFileCacheForRetrieval and set it to 0.
  • Enable\Allow to run Historian

 

missing trend historian data
Give feedback about this article

Recommended articles

[ISS Support Case] Historian Migration

Using TN Hist213 Migration of History Blocks to a New Server but within the configurator, the attempt lags upgraded from 10.0.0.1

Read More

[ISS Support Case] Historian data not showing

No Historian data is displaying for any tags prior to 5/8 at about 11:00 AM. Found no errors in the SMC log or Windows System log from 5/8 at midnight through 5/10 at 11:59 PM. There was a Historian warning in the Windows App log on 5/9 at 1:00 AM "Null value / quality mismatch - value / quality is overwritten to conform with OPC specification". No events were known to have happened on 5/8 that would have caused this issue. Have requested a reboot of our Historian server at 4:30 PM this afternoon to see if the problem would be resolved by a reboot. Would just like to check and see if there is any other investigation that could be performed or any other remedy that we might be able to perform to resolve the issue in lieu of a Historian server reboot.

Read More

TN HistClient135 Using Analog Statistics in Historian Client Query

Read More
Support Icon

CONTACT SUPPORT

How to reach us

10800 Midlothian Turnpike Tpke, Suite 209, Richmond, VA 23235

1.877.INSOURCE

Technical Support - 1.888.691.3858

Contact Us

  • InSource Solutions
  • InSource Training
  • InSource Client Portal
  • Log In
InSource Solutions Group Logo

© 2026 InSource Solutions. All Rights Reserved.

Knowledge Base Software powered by Helpjuice

Expand